These are homes that have not yet completed both Roughin & Final Inspection
Search
RI = Rough-In. FN = Final.
Builder Address Request (RI) Request (FN) Requester (RI) Requester (FN) Status (RI) Status (FN) Inspected (RI) Inspected (FN)
592-A Charity L...08/23/2018jessica wa...Not Ready--08/23/2018
Re-submit Roughin
Tech Comments (RI):Add insulation barrier on garage wall. add and seal top plate in dead space next to tub. -kp
Tech Comments (FN):
592-B Charity L...08/23/2018jessica wa...Not Ready--08/23/2018
Re-submit Roughin
Tech Comments (RI):Add insulation barrier over front porch and garage wall. add air barrier in dead space next to tub. add and seal top plate in dead space next to tub. -kp
Tech Comments (FN):
2707 Butler Rd ...04/01/2020jessicaNot Ready--04/13/2020
Re-submit Roughin
Tech Comments (RI):
Tech Comments (FN):
673 Jack thomas...05/12/2021daniel lop...Passed--05/14/2021
Submit Final
Tech Comments (RI):
Tech Comments (FN):
854 Mint spring...09/27/2021jessicaPassed--09/28/2021
Submit Final
Tech Comments (RI):1st floor 1. repair air barrier behind tub on north wall. air barrier must completely cover insulation. air barrier must extend to at least the top of the tub. 2. air barrier must completely cover insulation. attic wall space above firehouse. 3. add air barrier to attic wall above stairs. 4. air barrier must completely cover insulation. attic wall space by stairs. 5. seal blocking on garage band. 6. add staves to insulation above garage. 7. insulate garage band. 8. add additional eave baffles throughout house. at least at every third rafter.---------------1894sq ft first floor. 360sq ft second floor. 2254 total sq ft. single hvac unit.
Tech Comments (FN):
383 Bevills chu...11/29/2021jessica wa...Passed--12/01/2021
Submit Final
Tech Comments (RI):Upstairs. insulate under return duct in closet. add(raise) insulation barrier on attic wall. downstairs. insulate garden band on right side of garage. add air baffles in attic downstairs.
Tech Comments (FN):
537 Charity Ln ...12/03/2021jessica wa...----
Tech Comments (RI):1st floor 1. complete air barrier at raised wall. garage entry hallway and hallway west of living room. 2. complete air barrier at stairway. 3. seal penetrations and gaps in air barrier on attic wall by stairway. 4. add eave baffles throughout house. 5. add and seal air barrier at raised walls right of front door. 6. insulate raised wall at east side of living room. 7. add insulation barrier along east wall of living room. 2nd floor 1. add insulation barrier around stairway. 2. seal penetrations through blocking at stairway.
Tech Comments (FN):

© Copyright Huntsville Utilities Forms Support FAQ Supported Browsers Privacy Policy Terms of Use Site Map
Huntsville Utilities is an equal opportunity residential utility service provider. We do not discriminate in the terms, conditions, or provision of services based on race, color, religion, sex, disability, familial status, or national origin.

Huntsville Utilities es un proveedor de servicios residenciales publicos (electricidad, gas y agua) que ofrece igualdad de oportunidades. Nosotros no discriminamos en los terminos, las condiciones, o las provisiones de nuestros servicios basados en la raza, religion, color, sexo, discapacidad, estado familiar u origen nacional.